Search Results (795 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2024-9002 1 Schneider-electric 1 Easergy Studio 2024-10-15 7.8 High
CWE-269: Improper Privilege Management vulnerability exists that could cause unauthorized access, loss of confidentiality, integrity, and availability of the workstation when non-admin authenticated user tries to perform privilege escalation by tampering with the binaries
CVE-2024-8306 1 Schneider-electric 2 Vijeo Designer, Vijeo Designer Embedded In Ecostruxure Machine Expert 2024-09-18 7.8 High
CWE-269: Improper Privilege Management vulnerability exists that could cause unauthorized access, loss of confidentiality, integrity and availability of the workstation when non-admin authenticated user tries to perform privilege escalation by tampering with the binaries.
CVE-2024-6918 1 Schneider-electric 1 Accutech Manager 2024-09-03 7.5 High
CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists that could cause a crash of the Accutech Manager when receiving a specially crafted request over port 2536/TCP.
CVE-2011-5163 2 Mitsubishi-automation, Schneider-electric 2 Mx4 Scada, Citectscada 2024-08-07 N/A
Buffer overflow in an unspecified third-party component in the Batch module for Schneider Electric CitectSCADA before 7.20 and Mitsubishi MX4 SCADA before 7.20 allows local users to execute arbitrary code via a long string in a login sequence.
CVE-2011-4859 1 Schneider-electric 21 M340 Ethernet Module Bmxnoe0100, M340 Ethernet Module Bmxnoe0110, M340 Ethernet Module Bmxp342020 and 18 more 2024-08-07 N/A
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port.
CVE-2011-4034 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2024-08-06 N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to execute arbitrary code or cause a denial of service via unspecified vectors.
CVE-2011-4033 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2024-08-06 N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to cause a denial of service via unspecified vectors.
CVE-2011-4036 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2024-08-06 N/A
Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors.
CVE-2011-4035 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2024-08-06 N/A
Cross-site scripting (XSS) vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2011-3330 1 Schneider-electric 6 Monitor Pro, Opc Factory Server, Pl7 Pro and 3 more 2024-08-06 N/A
Buffer overflow in the UnitelWay Windows Device Driver, as used in Schneider Electric Unity Pro 6 and earlier, OPC Factory Server 3.34, Vijeo Citect 7.20 and earlier, Telemecanique Driver Pack 2.6 and earlier, Monitor Pro 7.6 and earlier, and PL7 Pro 4.5 and earlier, allows local users, and possibly remote attackers, to execute arbitrary code via an unspecified system parameter.
CVE-2011-3144 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2024-08-06 N/A
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2012-0930 1 Schneider-electric 1 Modicon Quantum Plc 2024-08-06 6.1 Medium
Cross-site scripting (XSS) vulnerability in Schneider Electric Modicon Quantum PLC allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2012-0929 1 Schneider-electric 1 Modicon Quantum Plc 2024-08-06 7.5 High
Multiple buffer overflows in Schneider Electric Modicon Quantum PLC allow remote attackers to cause a denial of service via malformed requests to the (1) FTP server or (2) HTTP server.
CVE-2012-0931 1 Schneider-electric 1 Modicon Quantum Plc 2024-08-06 9.8 Critical
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
CVE-2013-6143 1 Schneider-electric 1 Telvent Sage 3030 Firmware 2024-08-06 N/A
The Schneider Electric Telvent SAGE 3030 RTU with firmware C3413-500-001D3_P4 and C3413-500-001F0_PB allows remote attackers to cause a denial of service (temporary outage and CPU consumption) via malformed DNP3 traffic.