Search Results (795 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2022-41671 1 Schneider-electric 2 Ecostruxure Operator Terminal Expert, Pro-face Blue 2025-05-01 7 High
A CWE-89: Improper Neutralization of Special Elements used in SQL Command (‘SQL Injection’) vulnerability exists that allows adversaries with local user privileges to craft a malicious SQL query and execute as part of project migration which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior).
CVE-2022-41670 1 Schneider-electric 2 Ecostruxure Operator Terminal Expert, Pro-face Blue 2025-04-30 7 High
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in the SGIUtility component that allows adversaries with local user privileges to load malicious DLL which could result in execution of malicious code. Affected Products: EcoStruxure Operator Terminal Expert(V3.3 Hotfix 1 or prior), Pro-face BLUE(V3.3 Hotfix1 or prior).
CVE-2022-0222 1 Schneider-electric 28 Modicon M340 Bmxnoe0100, Modicon M340 Bmxnoe0100 Firmware, Modicon M340 Bmxnoe0110 and 25 more 2025-04-29 7.5 High
A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24)
CVE-2022-37301 1 Schneider-electric 96 Modicon M340 Bmx P34-2010, Modicon M340 Bmx P34-2010 Firmware, Modicon M340 Bmx P34-2030 and 93 more 2025-04-28 7.5 High
A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior)
CVE-2017-7970 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 N/A
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to specify Arbitrary Server Target Nodes in connection requests to the Secure Gateway and Server components.
CVE-2017-7971 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 N/A
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate.
CVE-2017-7965 1 Schneider-electric 1 Somachine Hvac 2025-04-20 7.3 High
A buffer overflow vulnerability exists in Programming Software executable AlTracePrint.exe, in Schneider Electric's SoMachine HVAC v2.1.0 for Modicon M171/M172 Controller.
CVE-2017-7974 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files.
CVE-2017-6028 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 9.8 Critical
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
CVE-2017-9958 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
An improper access control vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an improper handling of the system configuration can allow an attacker to execute arbitrary code under the context of root.
CVE-2017-7969 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 N/A
A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack.
CVE-2017-9956 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
An authentication bypass vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system contains a hard-coded valid session. An attacker can use that session ID as part of the HTTP cookie of a web request, resulting in authentication bypass
CVE-2017-9629 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 9.8 Critical
A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account.
CVE-2017-9957 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials.
CVE-2017-6026 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 9.1 Critical
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised.
CVE-2017-6032 1 Schneider-electric 2 Modbus, Modbus Firmware 2025-04-20 N/A
A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks.
CVE-2017-6030 1 Schneider-electric 6 Modicon M221, Modicon M221 Firmware, Modicon M241 and 3 more 2025-04-20 6.5 Medium
A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.
CVE-2017-9959 1 Schneider-electric 1 U.motion Builder 2025-04-20 N/A
A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the system accepts reboot in session from unauthenticated users, supporting a denial of service condition.
CVE-2017-7574 1 Schneider-electric 3 Modicon Tm221ce16r, Modicon Tm221ce16r Firmware, Somachine 2025-04-20 9.8 Critical
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.
CVE-2017-7972 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 N/A
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the ability to escape out of remote PowerSCADA Anywhere applications and launch other processes.